Networking for SI

Networking for SI, Part 2: The Four Networks in an SI Cluster

What the four networks in an SI cluster carry, why storage stays off the GPU fabric, and how to size it from MLPerf Storage's checkpoint test.

On this page 11 sections

An SI training cluster runs on several networks at once. NVIDIA’s reference architecture for the DGX SuperPOD with GB200 runs five network fabrics on four physical ones, and Meta runs its training clusters on two independent networks. In both designs, storage traffic stays off the fabric the GPUs use to talk to each other.

The four networks in an SI cluster: scale-up inside each rack, the back-end between racks, storage, and the front-endA row of six racks of GPU trays. A copper bar runs down the middle of each rack for its scale-up links. A dashed copper line above the racks joins them all for the back-end network. Below the racks, a teal line runs to a block of storage on the right, and a dashed mint line runs to a block for users and management on the left.GUIDE / NETWORKING FOR SI, PART 2Four networks, one clusterSCALE-UP · BACK-END · STORAGE · FRONT-ENDBACK-ENDSCALE-UPFRONTENDSTORAGE

Part 1 covered NVMe over Fabrics (NVMe-oF), which carries storage commands across a network. This part asks what each network around it carries, why storage is kept apart from GPU traffic, and how much bandwidth storage needs. For the last question it works from the checkpoint workload in MLPerf Storage. That MLCommons benchmark times how fast a storage system saves and restores a training checkpoint.

Four networks, one cluster

Vendors name these networks differently, so this guide uses four plain names. Scale-up joins GPUs inside one domain. Back-end scale-out joins GPUs across servers and racks, storage reaches shared storage, and the front-end carries what users and administrators touch. Meta’s back-end runs RoCE, which carries remote direct memory access (RDMA) over Ethernet.

This guide NVIDIA GB200 SuperPOD Meta’s clusters
Scale-up NVLink 5, one 72-GPU domain per rack NVLink in each eight-GPU server
Back-end Compute fabric, InfiniBand Back-end, RoCE
Storage Storage fabric, RoCE, shared Ethernet Front-end
Front-end In-band network, same Ethernet Front-end

Sources: NVIDIA DGX SuperPOD reference architecture with GB200, chapters 3 and 4, Meta’s post on RoCE networks for distributed AI training at scale, and the Llama 3 paper, section 3.3.1.

NVIDIA also runs a fifth network for out-of-band management. It reaches the baseboard management controller (BMC) and management port of every server, switch, storage system, and rack power distribution unit. In its B200 reference architecture, NVIDIA keeps it apart because no user ever needs those ports, and it carries no training or storage data.

Four networks, one cluster

One GB200 tray connects to four networks and a management one

Back-end on its own cards, storage and front-end on the BlueField-3 cards, NVLink inside the rack.

A schematic of one DGX GB200 compute tray. Inside are two GB200 Superchips, each with two B200 GPUs and one Grace CPU, above a row of four ConnectX-7 cards and two BlueField-3 cards. On the left, a dashed copper line runs from the ConnectX-7 cards to the back-end compute fabric, InfiniBand NDR at 400Gb/s per card, a fabric of its own. On the right, the BlueField-3 cards run a teal line to the storage network, RoCE on its own VXLAN segment, and a dashed mint line to the front-end in-band network, both on one Ethernet fabric at 2×200Gb/s. Below, a thick copper line runs to the NVLink switch trays, the scale-up network inside the rack, at 1.8TB/s per GPU. Above, a dotted line runs from the tray to the out-of-band network for the BMC ports.OUT-OF-BANDBMC portsGB200 COMPUTE TRAYSUPERCHIPB200B200Grace CPUSUPERCHIPB200B200Grace CPUConnectX-7 ×4BlueField-3 ×2BACK-ENDcompute fabricInfiniBand NDR400Gb/sper card, a fabricof its ownSTORAGERoCE on VXLANFRONT-ENDin-bandmanagement2×200Gb/s, both onone Ethernet fabricSCALE-UPNVLink switch trays1.8TB/s per GPUscale-upback-endstoragefront-endout-of-band
Figure 2.1 · The ports of one DGX GB200 compute tray and the network each one reaches. Source: NVIDIA DGX SuperPOD reference architecture with GB200, sections 3.1 and 4.

Each GB200 compute tray holds two GB200 Superchips, which makes four B200 GPUs and two Grace CPUs. Four ConnectX-7 network interface cards (NICs) run InfiniBand NDR at 400Gb/s for the compute network, and two BlueField-3 cards supply 2×200Gb/s for the in-band and storage networks. NVLink leaves the tray through blind-mate connectors at the back of the rack and runs only to the switch trays in that rack. Every other network leaves through cards and ports on the tray itself.

Scale-up stays inside the rack

In a DGX GB200 NVL72 rack, all 72 GPUs share one NVLink domain. Inside it are 18 compute trays and nine NVLink switch trays with two switch chips each. Every B200 GPU has 18 NVLink 5 links and runs one to each of the 18 switch chips, for 1.8TB/s per GPU.

Scale-up stays inside the rack

Every GPU in the rack has a link to every NVLink switch chip

One GPU's 18 links are drawn. The other 71 GPUs have the same fan.

A schematic of one GB200 NVL72 rack. Across the top, 18 compute trays each hold four GPUs, 72 in all. Across the bottom, nine NVLink switch trays each hold two switch chips, 18 in all. From one highlighted GPU, 18 copper lines fan out, one to each switch chip. Notes say one B200 GPU has 18 NVL5 links, one link per chip, for 1.8TB/s per GPU. Every other GPU has the same set of links, so any GPU reaches any other through a single switch chip.18 COMPUTE TRAYS · 72 GPUSone B200 GPU18 NVL5 linksone link per chip1.8TB/s per GPU9 NVLINK SWITCH TRAYS · 18 SWITCH CHIPSB200 GPUNVLink switch chipone GPU’s 18 links
Figure 2.2 · The NVLink domain of one DGX GB200 NVL72 rack: 72 GPUs, 18 switch chips, one link from each GPU to each chip. Source: NVIDIA DGX SuperPOD reference architecture with GB200, section 4.1.

NVIDIA calls this full-mesh connectivity. Because every GPU has a link to every switch chip, this guide reads it as any GPU reaching any other in the rack through one switch chip. NVIDIA’s parts table describes the NVLink switches as giving direct memory access between GPUs on the same rack, which suggests one GPU can reach another’s memory without a NIC in the path. That memory is HBM, which Working Memory Part 4 covers.

Not every vendor uses scale-up this way. Meta’s post on its RoCE networks uses it for the Ethernet switch that joins GPUs within one rack, below a spine tier it calls scale-out. In this guide’s terms, Meta’s scale-up domain is the NVLink inside each eight-GPU server, and that rack switch belongs to its back-end. In NVIDIA’s design the scale-up domain is NVLink too, and the storage ports sit on the BlueField-3 cards instead.

The back-end fabric between racks

GPU-to-GPU traffic between racks runs on the back-end network, which NVIDIA calls the compute fabric. For GB200 that network is InfiniBand NDR, which peaks at 400Gb/s per direction, and it is rail-aligned. A tray has four rails, so each of its GPUs has its own. A scalable unit (SU) of eight racks and 576 GPUs gives every rail its own group of switches, with eight leaf switches, one per rack, under six spine switches.

The back-end fabric between racks

Each rail has its own switches, and racks meet at the spine

Rail 1 of one scalable unit: eight racks, one leaf switch per rack, six spine switches above.

A schematic of one rail of the back-end compute fabric in a GB200 scalable unit. Across the bottom are eight racks, each drawn with the four GPUs of one tray; the first GPU of each is teal and links up to that rack's leaf switch for rail 1. The eight leaf switches each link to all six spine switches across the top. A thick copper path runs from the first GPU in rack 1 up to its leaf switch, up to a spine switch, down to the leaf switch of rack 5 and down to the first GPU there, showing that traffic between racks crosses the spine. A note says rails 2 to 4 each have their own group of leaf and spine switches.RAIL 1 · 8 LEAF SWITCHES · 6 SPINE SWITCHESrails 2 to 4 each have a group like this onespinespinespinespinespinespineleafrack 1leafrack 2leafrack 3leafrack 4leafrack 5leafrack 6leafrack 7leafrack 8rail 1 GPUGPU on rails 2 to 4linkpath between racks
Figure 2.3 · One rail of the GB200 SuperPOD compute fabric for one scalable unit. Rails 2 to 4 each have a switch group like it. Source: NVIDIA DGX SuperPOD reference architecture with GB200, section 4.2.

Within a rack, the trays reach each other on a rail through that rack’s leaf switch. NVIDIA routes traffic between different racks, or between different rails, through the spine layer. A message from the first GPU of a tray in one rack to the first GPU of a tray in another rack climbs from one leaf switch to a spine and back down to the other rack’s leaf.

Meta runs both kinds. According to its Llama 3 paper, Llama 3 405B trained on a RoCE fabric and the smaller Llama 3 models on InfiniBand, both with 400Gb/s links between GPUs. Meta’s network post describes the back-end as a non-blocking fabric between every RDMA NIC, and the paper qualifies that for its 24,000-GPU RoCE cluster. Pods of 3,072 GPUs have full bisection bandwidth, the aggregation layer above the pods is oversubscribed 1:7, and Meta’s scheduler and model parallelism keep communication inside a pod.

NVIDIA’s B200 reference architecture sets out the storage fabric’s job plainly. It is independent of the compute fabric, gives each DGX B200 at least 40GB/s, and runs over InfiniBand or RoCE. Storage systems connect at a 1:1 port-to-uplink ratio. On the server side, DGX B200 connections are oversubscribed near 4:3, so the server-facing ports add up to about a third more than their switches’ uplinks.

GB200 trays get a storage line rate of 2×200Gb/s each, again over RoCE. The front-end, which NVIDIA calls the in-band management network, handles node provisioning, data movement, Internet access, and the services users reach, at 200Gb/s bonded. NVIDIA also expects a Network File System (NFS) share on that network for home directories, scratch space, and logs, and sets 100Gb/s as its minimum.

Storage and front-end links

Per GPU, the storage share is a quarter of the compute link

NVLink is NVIDIA's total, the links are per direction. One GB200 tray over its four GPUs, log scale.

A horizontal bar chart on a logarithmic axis of gigabytes per second per GPU. NVLink, the scale-up network, gives each GPU 1.8TB/s. The compute link of the back-end network gives 50GB/s, which is 400Gb/s, one ConnectX-7 card per GPU. The storage share is 12.5GB/s, which is 100Gb/s, because four GPUs share 2×200Gb/s of storage line rate. NVIDIA gives NVLink as a total and the network links per direction; on those numbers NVLink is 36 times the compute link, and the compute link is four times the storage share.Network1101001,00010,000Bandwidth per GPU, GB/s, log scaleNVLinkscale-up1.8TB/sCompute linkback-end50GB/sStorage sharestorage network12.5GB/sscale-upback-endstorage network
Figure 2.4 · Bandwidth per GPU on three networks of a DGX GB200 tray, with the compute and storage shares as line rates divided by four GPUs. Source: NVIDIA DGX SuperPOD reference architecture with GB200, sections 3.1, 3.5 and 4.1.

Divided per GPU, the storage share is the smallest. A tray’s four GPUs split 2×200Gb/s of storage line rate, so each gets 100Gb/s. Each GPU has its own 400Gb/s compute link and 1.8TB/s of NVLink. NVLink’s figure is a total and InfiniBand’s is per direction, so the comparison mixes bases. On those numbers, NVLink is 36 times the compute share, and the compute share is four times the storage share.

Each tray also carries four 3.84TB E1.S drives in a RAID0 set, which NVIDIA lets users put to work caching or staging data. A dataset cached there on its first read doesn’t have to cross the storage network again.

Why storage stays off the GPU fabric

In the B200 design, NVIDIA keeps storage on a fabric independent of the compute fabric to maximize performance of both storage and application work. With GB200 it kept that split and merged storage with the front-end instead. Storage and in-band management now share one Ethernet fabric. NVIDIA made that change for cost-efficiency. Storage runs on its own Virtual Extensible LAN (VXLAN) segment and takes two of the four ports on each BlueField-3 card.

Each SU carries 16×800Gb/s of non-blocking bandwidth to the storage systems, while the server side blocks at 5:3. RoCE is a basic requirement for those storage systems, and NVIDIA relies on congestion control and adaptive routing in the switches to hold latency down.

Why storage stays off the GPU fabric

All three designs keep storage off the GPU-to-GPU fabric

DGX B200 splits everything, DGX GB200 joins storage to the front-end, Meta runs two networks.

Three panels, each with a column of GPU servers on the left linked to the fabrics on the right. Panel 1, DGX B200: three separate fabrics, the compute fabric on InfiniBand, the storage fabric on InfiniBand or RoCE, and the in-band network on Ethernet; storage has a fabric of its own. Panel 2, DGX GB200: the compute fabric on InfiniBand on its own, and a dashed outline around storage, on its own VXLAN segment, and the in-band network, which share one Ethernet fabric. Panel 3, Meta: a back-end on RoCE for training, and a front-end that carries data ingestion, checkpoints, and logging. In every panel the GPU-to-GPU fabric carries no storage traffic.01 DGX B200GPUserverscomputeInfiniBandstorageInfiniBandor RoCEin-bandEthernetstorage has afabric of its own02 DGX GB200GPUserverscomputeInfiniBandstorageown VXLANin-bandstorage shares oneEthernet fabric03 METAGPUserversback-endRoCEfront-endingestioncheckpointsloggingcheckpoints ridethe front-endGPU-to-GPU fabricstoragefront-endone shared fabric
Figure 2.5 · Where storage traffic sits in NVIDIA's DGX B200 and GB200 SuperPOD designs and in Meta's training clusters. Source: NVIDIA DGX SuperPOD reference architectures with B200 and GB200, and Meta, RoCE networks for distributed AI training at scale.

Meta draws the line in the same place with fewer networks. Its front-end carries data ingestion, checkpointing, and logging, and the back-end carries only training traffic between RDMA NICs. Meta tunes the two differently. Meta calls Data Center Quantized Congestion Notification (DCQCN) the gold standard for storage-focused networks, yet it ran its 400G training back-end for over a year on Priority-based Flow Control (PFC) alone, with DCQCN turned off.

Checkpoints are the traffic that makes the split worth having. According to the Llama 3 paper, checkpoint writes are highly bursty and saturate the storage fabric for short durations. On a shared fabric, that burst would queue in the same switch buffers as the training job’s GPU-to-GPU exchanges, and Part 1 covers what happens when many senders hit one receiver. Both designs put the boundary between GPU-to-GPU traffic and everything else, and this guide reads that as the boundary that matters. A storage network can share a fabric with management traffic, but in neither design does it share one with the training job’s own collectives.

Sizing the storage network from a checkpoint

MLCommons added a checkpoint workload to MLPerf Storage in version 2.0, announced August 4, 2025. It builds the model and optimizer state of a Llama 3 model in memory, saves and loads it with PyTorch, and times the storage system underneath. That makes it a measured stand-in for the burst the storage network has to carry, and Part 1 showed how long a job can wait on that path when storage bandwidth is short.

What a checkpoint holds

The benchmark fixes four model sizes, each with a set process count and checkpoint size. Table 2 of the rules labels the sizes GB and TB but counts them in binary units, so MLCommons’ results page gives them in GiB.

Model Processes Approximate size
Llama 3 8B 8 105GiB
Llama 3 70B 64 911GiB
Llama 3 405B 512 5,290GiB
1T (1250B in results) 1,024 18,000GiB

Sources: MLPerf Storage benchmark results page, checkpointing workload table, and MLPerf Storage Benchmark Rules, Table 2.

Most of that is optimizer state. MLCommons’ workload post says the 8B checkpoint totals 105GB, of which 90GB is optimizer state, and that model and optimizer state stay the same size as more data-parallel copies are added. By that rule, a 405B checkpoint stays about 5,290GiB whether 512 GPUs train the model or 16,000 do.

The 405B model runs with tensor, pipeline, and data parallelism of 8×32×2, so its 512 processes each write about 10.3GiB. That sits inside the 9 to 20GiB per process given on the results page. Every write ends with an fsync. A run saves 10 checkpoints before it reads 10 back, and each client host is expected to write more than three times its memory, so the client’s RAM can’t hide the storage.

How long training can wait

Synchronous training stops while a checkpoint is written, and NVIDIA’s GB200 guide says the same of its own clusters. Failures decide how often a checkpoint is needed. During a 54-day stretch of Llama 3 405B pre-training on up to 16,000 H100 GPUs, Meta counted 419 unexpected interruptions. MLCommons built a failure model on that data, and it predicts 7.67 failures a day at 16,000 accelerators against the 7.76 observed.

MLCommons then applies a rule of thumb from its checkpoint workload post. Losing 5% or less of progress is reasonable, which means about 20 checkpoints between expected failures. At 16,000 accelerators it estimates 155 checkpoints a day. That is one every 9.3 minutes, and keeping the overhead under 5% leaves 28 seconds to write each one. At 100,000 accelerators it is 967 a day, every 1.5 minutes, with 4.4 seconds per checkpoint.

The write rate that follows

Storage must absorb the checkpoint size divided by the time allowed:

write rate = checkpoint size / time allowed

Checkpoint size is in GB, time allowed is in seconds, and the write rate comes out in GB/s. Network rates are decimal, so the 405B checkpoint’s 5,290GiB becomes about 5,680GB here. Inside the 28-second budget that is 5,680GB / 28 seconds, or about 203GB/s. At 4.4 seconds it is about 1,291GB/s, roughly 1.3TB/s. Both are MLCommons’ budgets applied to MLPerf’s 405B checkpoint, so they are estimates, not any cluster’s measurement. The second pairs that checkpoint with the budget for a far larger cluster, so it shows scale rather than a real job.

Sizing the storage network from a checkpoint

A 405B checkpoint in 28 seconds needs about 203GB/s of writes

Needed rates are estimates from MLCommons' budgets. Meta's Llama 3 storage fabric is shown for scale.

A horizontal bar chart of write rate in gigabytes per second. Two hollow, dashed bars are estimates: writing MLPerf's 405B checkpoint of about 5,680GB inside the 28-second budget MLCommons gives a 16,000-accelerator cluster needs about 203GB/s, and inside the 4.4-second budget for 100,000 accelerators about 1,291GB/s. Two solid bars are Meta's published figures for its Llama 3 storage fabric: 2TB/s sustained and 7TB/s peak.Need or capacity02,0004,0006,0008,000Write rate, GB/s28-second budget16,000 accelerators203GB/s4.4-second budget100,000 accelerators1,291GB/sMeta storage fabricsustained2TB/sMeta storage fabricpeak7TB/sneeded, estimateMeta fabric, published
Figure 2.6 · Write rate needed for MLPerf's 405B checkpoint inside MLCommons' time budgets, beside Meta's published storage throughput. Source: MLCommons checkpoint workload post and results page, and the Llama 3 paper, section 3.3.1.

For scale, Meta’s Llama 3 storage fabric, built on its Tectonic file system, offered 240PB on 7,500 SSD servers with 2TB/s sustained and 7TB/s peak throughput. At the sustained rate, 5,680GB would take about 2.8 seconds. That divides one source’s throughput by another’s checkpoint size, so it is arithmetic, not a measured save.

Per GPU, the numbers are small. Spread across 16,000 GPUs, 5,680GB is about 355MB each, inside the 1MB to 4GB per GPU that the Llama 3 paper reports, and writing it in 28 seconds takes about 13MB/s per GPU. At this scale the limit is the aggregate rate the storage end can absorb when every writer starts at once, not the per-GPU link. A save in MLPerf is done only when every process is done, so the slowest writer sets the finish.

One scalable unit, worked through

The 405B workload’s 512 processes fit inside one GB200 SU of 576 GPUs, which makes NVIDIA’s own numbers a fair check. Its 16 storage-side links of 800Gb/s add up to 1,600GB/s. NVIDIA’s storage guidelines for one SU are far lower, with 20GB/s of aggregate write at its standard level and 62GB/s at enhanced, against 40GB/s and 125GB/s of read. NVIDIA also advises write performance of at least half the read performance for large models.

Sizing the storage network from a checkpoint

The storage system, not the link, sets how long a checkpoint takes

One GB200 scalable unit writing MLPerf's 405B checkpoint of about 5,680GB.

A horizontal bar chart of seconds to write MLPerf's 405B checkpoint of about 5,680GB in one GB200 scalable unit. At the unit's storage-side line rate of 1,600GB/s it takes about 3.6 seconds, a sliver of a bar. At NVIDIA's enhanced write guideline of 62GB/s it takes about 92 seconds, and at the standard guideline of 20GB/s about 284 seconds. The network links are about 26 times faster than the enhanced guideline, so the storage system sets the stall.Write rate0100200300Time to write the checkpoint, secondsstorage link rate1,600GB/s3.6 secondsenhanced guideline62GB/s write92 secondsstandard guideline20GB/s write284 secondsline rate to storageNVIDIA write guideline
Figure 2.7 · Time to write the 405B checkpoint in one scalable unit at its storage-side line rate and at NVIDIA's two write guidelines. Source: NVIDIA DGX SuperPOD reference architecture with GB200, section 4.4.1 and Table 5.2, and MLCommons' results page.

Writing 5,680GB takes about 3.6 seconds at the SU’s 1,600GB/s storage-side line rate, about 92 seconds at the enhanced 62GB/s, and about 284 seconds at the standard 20GB/s. That storage-side capacity is about 26 times the enhanced write rate NVIDIA plans the storage system to deliver. In this design the stall is set by how fast the storage system completes durable writes, which is what MLPerf’s fsync rule and its write duration, the time training would stall, measure.

Sizing the storage network from link rates alone would promise checkpoints far faster than the storage behind it can finish them. The better sizing input is a published 405B write duration for the storage system being bought, compared only with other 405B rows, as MLCommons advises.

What to watch

Faster checkpoints change this arithmetic. On its GenAI training clusters, Meta has optimized checkpointing across thousands of ranks to run in hundreds of milliseconds, a pattern the synchronous, fsync-bound save that MLPerf times leaves out. MLPerf’s subset mode tests another shortcut. It puts the first checkpoint tier on an NVMe drive in each node and uses 8 processes. MLCommons notes that subset mode doesn’t give full fault tolerance without a secondary storage solution or extra software, so a copy still has to reach shared storage.

What to watch

Three ways checkpoints reach storage, and one rule change

MLPerf times the first. The other two move or shorten the burst.

Three panels. Panel 1, synchronous save: four process boxes each send a copper arrow down to one shared storage box; notes say a run makes 10 saves then 10 reads, each write ends with an fsync, and the slowest process sets the end of each save. Panel 2, local first tier: a node box holds an NVMe drive in teal, and a dashed copper arrow runs from it to a shared storage box; notes say subset mode uses 8 processes and a copy still has to reach shared storage. Panel 3, faster saves: a grid of many small rank boxes sends one short arrow to storage; notes say Meta reports checkpointing across thousands of ranks in hundreds of milliseconds. A band along the bottom says that from rules edition 4.0, checkpoint rows compare only within one accelerator.01 SYNCHRONOUS SAVEshared storage10 saves, 10 readsfsync on each writeslowest sets the end02 LOCAL FIRST TIERshared storagesubset mode8 processescopy still needed03 FASTER SAVESshared storagethousands of rankshundreds ofmillisecondsNODENVMerules edition 4.0: checkpoint rows compare within one acceleratorstorageprocess, node or rankcheckpoint dataplanned rule
Figure 2.8 · The synchronous save MLPerf Storage measures, the local first tier its subset mode tests, and the faster saves Meta reports, with the rules change due in edition 4.0. Source: MLCommons checkpoint workload post and benchmark rules, and Meta, Building Meta's GenAI infrastructure.

The rules are moving too. From edition 4.0, MLPerf Storage will compare checkpoint results only within one emulated accelerator, so NVIDIA B200 and AMD MI355 rows will stop lining up. Until then, a 405B write duration from the published results is the closest public stand-in for the stall a storage system adds.